C106053 (EN)
|
Gypframe 60 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
120
|
2500
|
N/A
|
60
|
60
|
42
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106054 (EN)
|
Gypframe 92 I 90 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
152
|
3000
|
N/A
|
60
|
60
|
44
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106055 (EN)
|
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
206
|
4000
|
N/A
|
60
|
60
|
48
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106056 (EN)
|
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
422
|
4000
|
N/A
|
120
|
120
|
48
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106057 (EN)
|
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres
|
1 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
397
|
4400
|
N/A
|
90
|
90
|
48
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106058 (EN)
|
Gypframe 70 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
130
|
2800
|
N/A
|
60
|
60
|
42
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106059 (EN)
|
Gypframe 60 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
120
|
2500
|
25mm Isover Acoustic Partition Roll (APR 1200)
|
60
|
60
|
45
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106060 (EN)
|
Gypframe 70 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
130
|
2800
|
25mm Isover Acoustic Partition Roll (APR 1200)
|
60
|
60
|
45
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106061 (EN)
|
Gypframe 92 I 90 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
152
|
3000
|
25mm Isover Acoustic Partition Roll (APR 1200)
|
60
|
60
|
46
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|
|
C106062 (EN)
|
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
|
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
|
N/A
|
N/A
|
206
|
4400
|
25mm Isover Acoustic Partition Roll (APR 1200)
|
60
|
60
|
50
|
close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
You will need to register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files
Close
ShaftWall
Shaft and duct encasement system.
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.
- Horizontal membranes are built entirely from below
- A ShaftWall variant with non-combustible Glasroc F FireCase board linings is available
- High level commonality with GypWall partition components, particularly 70mm stud solutions
- Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
- Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors
Is Gyproc FireStrip required
Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.
How do you build a fire-rated partition where access is limited to one side only?
Our ShaftWall system is designed for this application.
What are Staggered, Quiet, Quiet SF, Audio, ShaftWall stud partitions?
These are all types of British Gypsum metal stud partition systems, each with a different application.
|