Horizontal Shaftwall

A free-spanning membrane with no support from the soffit

Shaftwall can be specified for horizontal applications as a free-spanning membrane with no support from the soffit. The membrane can be constructed entirely from below and can achieve spans up to 5100mm and fire resistance up to 120 minutes. A typical application is for fire escape corridors. Supporting partitions should be of at least the same fire resistance period as the horizontal Shaftwall.

Please note that all British Gypsum Drylining systems are tested to the BS EN fire test standard. However we can continue to support your BS Standard Specifications project with remaining test evidence to BS 476. Please click here for more information.

 

Watch this short video to see how to use this EN Specification Selector and where you can still get details of our BS Specifications.

Filter your results
Apply filters
Filter
Fire Integrity (mins)
min
max
Fire Insulation (mins)
min
max
Maximum Span (mm)
min
max
Sound Insulation (Airborne) Rw (dB)
min
max
4 Solutions

C106058 (EN)

Horizontal framework comprising of Gypframe 70 I 70 ‘I’ Studs at 600mm centres with Gyproc CoreBoard 19mm between studs, secured by Gypframe G110 Retaining Channel. Gypframe MF5 Ceiling Sections fixed perpendicular to Gypframe 'I' Studs on ceiling side at 450mm centres. Two layers of Gyproc FireLine 15mm to ceiling side.

Fire Integrity (mins)
60
Fire Insulation (mins)
60
Sound Insulation (Airborne) Rw (dB)
42
Maximum Span (mm)
2800
System Depth (mm)
130

C106058 MR1 (EN)

Horizontal framework comprising of Gypframe 70 I 70 ‘I’ Studs at 600mm centres with Gyproc CoreBoard 19mm between studs, secured by Gypframe G110 Retaining Channel. Gypframe MF5 Ceiling Sections fixed perpendicular to Gypframe 'I' Studs on ceiling side at 450mm centres. Inner layer of Gyproc FireLine 15mm and an outer layer of Gyproc FireLine MR 15mm to ceiling side.

Fire Integrity (mins)
60
Fire Insulation (mins)
60
Sound Insulation (Airborne) Rw (dB)
42
Maximum Span (mm)
2800
System Depth (mm)
130

C106060 (EN)

Horizontal framework comprising of Gypframe 70 I 70 ‘I’ Studs at 600mm centres with Gyproc CoreBoard 19mm between studs, secured by Gypframe G110 Retaining Channel. Gypframe MF5 Ceiling Sections fixed perpendicular to Gypframe 'I' Studs on ceiling side at 450mm centres. Two layers of Gyproc FireLine 15mm to ceiling side and 25mm Isover Acoustic Partition Roll (APR 1200) in the cavity.

Fire Integrity (mins)
60
Fire Insulation (mins)
60
Sound Insulation (Airborne) Rw (dB)
45
Maximum Span (mm)
2800
System Depth (mm)
130

C106060 MR1 (EN)

Horizontal framework comprising of Gypframe 70 I 70 ‘I’ Studs at 600mm centres with Gyproc CoreBoard 19mm between studs, secured by Gypframe G110 Retaining Channel. Gypframe MF5 Ceiling Sections fixed perpendicular to Gypframe 'I' Studs on ceiling side at 450mm centres. Inner layer of Gyproc FireLine 15mm and an outer layer of Gyproc FireLine MR 15mm to ceiling side and 25mm Isover Acoustic Partition Roll (APR 1200) in the cavity.

Fire Integrity (mins)
60
Fire Insulation (mins)
60
Sound Insulation (Airborne) Rw (dB)
45
Maximum Span (mm)
2800
System Depth (mm)
130