A free-spanning membrane with no support from the soffit

Close

ShaftWall can be specified for horizontal applications as a free-spanning membrane with no support from the soffit. The membrane can be constructed entirely from below and can achieve spans up to 5100mm and fire resistance up to 120 minutes. A typical application is for fire escape corridors. Supporting partitions should be of at least the same fire resistance period as the horizontal ShaftWall.

12 result(s) found.

Show filters Hide filters
Export results as .csv
System System Ref Lower framework Lower framework boarding Upper framework Upper framework boarding System depth (mm) Max span (mm) Insulation Fire Integrity (mins) Fire Insulation (mins) Sound Insulation
Rw dB
Go to basket
C106053 (a)
Gypframe 60 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
120
2500
N/A
60
60
42

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106053 (b)
Gypframe 60 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
120
2500
25mm Isover Acoustic Partition Roll (APR 1200)
60
60
45

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106053 (c)
Gypframe 70 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
130
2800
N/A
60
60
42

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106053 (d)
Gypframe 70 I 70 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
130
2800
25mm Isover Acoustic Partition Roll (APR 1200)
60
60
45

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106054 (a)
Gypframe 92 I 90 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
152
3700
N/A
60
60
44

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106054 (b)
Gypframe 92 I 90 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
152
3700
25mm Isover Acoustic Partition Roll (APR 1200)
60
60
46

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106055 (a)
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
206
5100
N/A
60
60
48

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106055 (b)
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
N/A
N/A
206
5100
25mm Isover Acoustic Partition Roll (APR 1200)
60
60
50

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106056 (a)
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
422
5100
N/A
120
120
48

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall

C106056 (b)
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres & Gypframe MF5 Ceiling Sections @ 450mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
Gypframe 146 TI 90 Tabbed 'I' Stud @ 600mm centres
2 x 15mm Gyproc FireLine (+ 19mm Gyproc CoreBoard in cavity)
422
5100
25mm Isover Acoustic Partition Roll (APR 1200)
120
120
50

close
ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.


You will need register and login to access premium files such as NBS (word & PDF), .dwg CAD, and .rvt BIM files

Close ShaftWall

ShaftWall

Shaft and duct encasement system.

ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The system can also be built horizontally to provide a fire rated membrane.

  • Horizontal membranes are built entirely from below
  • A ShaftWall variant with non-combustible Glasroc F FIRECASE board linings is available
  • High level commonality with GypWall partition components, particularly 70mm stud solutions
  • Higher certainty of installed acoustic performance due to laboratory tests incorporating deflection heads
  • Can be used where access is limited to one side at the head, e.g. M & E cages already installed in corridors

Is Gyproc FireStrip required

Where included in the detail, Gyproc FireStrip is an essential component in maintaining the fire resistance of a partition.

How do you build a fire-rated partition where access is limited to one side only?

Our ShaftWall system is designed for this application.

What are STAGGERED, QUIET, QUIET SF, AUDIO, ShaftWall stud partitions?

These are all types of British Gypsum metal stud partition systems, each with a different application.

How To - Install ShaftWall